Practical IEC 61850 and substation engineering calculators. Results are indicative — always verify against your project specifications and the applicable IEC standard.

⏱️ GOOSE Retransmission Schedule
Results will appear here.

Intervals double each retransmission from T₀ until maxTime is reached. TAL = 2× current interval.

🔢 APPID Range Validator
Enter an APPID to validate.

Per IEC 61850-8-1 Ed. 2. APPID must be unique within each VLAN segment.

🌐 VLAN Tag Decoder
Enter a 4-hex-digit TCI value.

TCI = PCP (3 bits) + DEI (1 bit) + VID (12 bits). GOOSE requires PCP ≥ 4.

🕐 IEC 61850 UtcTime Decoder
Paste the 8 hex bytes from a GOOSE frame.

Bytes 0–3: seconds since 1970-01-01 00:00:00 UTC. Bytes 4–6: sub-second (fraction of 2²⁴). Byte 7: quality flags.

🔌 CT Burden Calculator
Fill in CT parameters above.

Checks whether the CT secondary burden is within the rated burden for the selected class.

📶 GOOSE Bandwidth Estimator
Fill in parameters above.

Steady-state heartbeat load + worst-case burst on simultaneous state changes (6 retransmissions modelled).

🔗 Object Reference Builder
Fill in fields above.

Builds an IEC 61850 object reference in the form IEDName/LDname/LNname.DOname.DAname[FC].

📝 confRev Mismatch Checker
Enter both confRev values.

Per IEC 61850-8-1 Ed. 2: mismatch means the publisher was reconfigured after the subscriber's SCD was compiled. Subscriber should raise an alarm.